Troubleshooting and repair

General problems

Problem Cause/solution
Device does not respond (status LED always off).
Communication problems
  • Load the device log from the myDatalogEASY IoT ATEX using the DeviceConfig (see "Log" tab). A list of all the possible error codes is included in the chapter "Log entries and error codes" (see Log entries and error codes).
  • The capacity of the energy store in the power supply unit is virtually depleted.
The connection via the external SIM card is not working.
  • The chargeable feature "Activation code VPN SIM (300539)" has not been released.
  • Check whether the external SIM card has been inserted correctly (see Inserting/replacing the SIM card).
  • Check whether the configuration data (PIN, APN, username and password) have been set correctly via the DeviceConfig (see "GSM" tab).
  • Check whether the PIN code (if required by the SIM card) has been set correctly by the DeviceConfig .
Not all or no data is available on the server.
  • The connection was aborted during the transmission, which is indicated by a time-out entry in the connection list (see "myDatanet Server Manual " 805002). Solution: Initiate a transmission or wait for the next cyclical transfer.
  • The assignment of the device and site is not correct (see Site).
Data at universal input is not plausible.
The alarm state of a measurement channel was not identified.
  • Increase the measurement cycle
The alarm state was not transmitted although the data is present.
  • Check the alarm settings of the measurement channel
  • The connection was aborted during the transmission, which is indicated by a time-out entry in the connection list (see "myDatanet Server Manual " 805002). Solution: Initiate an Aloha transmission or wait for the next cyclical transmission.
The alarm message was not sent although the alarm was signalled.
  • Check the settings of the alarm schedule (see "myDatanet Server Manual " 805002)
  • Check the address data of the alarm schedule (see "myDatanet Server Manual " 805002)