Level

This configuration section is used to configure the settings for generating the main level and the two sub levels.

Configuration section "Level"

Information about the main level
1 Status information about the main level

By clicking on this area, the input window containing the settings for the generation of the main level is opened (see Main Level settings).

2 Name used for the measurement channel of the main level
3 Measurement value type

Information about a sub level
4 Status information about one of the sub levels

By clicking on this area, the input window containing the settings for the generation of the sub level is opened (see Sub Level settings).

5 Name used for the measurement value of the sub level
6 Measurement value type
7 Mode used for the calculation of the sub level
Off Calculation of the sub level deactivated
Distance The distance provided by the sensor is subtracted from the mounting height

Sub level = mounting height - distance

Absolute pressure compensated The sub level is calculated in several stages:
  • Determining the difference between pressure in the medium and atmospheric pressure
  • Converting the differential pressure to the water column height
  • Adding the mounting height to the water column height

Sub level = (pressure in the medium - atmospheric pressure) x 10,1936799 + nounting height