Compatible sensors
Microtronics Engineering GmbH is constantly testing various sensors with mA output for compatibility with the myDatalogEASY IoT ATEX . If your sensor is not on the list, please contact us at support@microtronics.com. We then check whether your sensor can be used together with the myDatalogEASY IoT ATEX and determine the Zener barrier to be used, the recommended configuration settings and the expected battery lifespan.
| Manufacturer | Designation | Type | Zener barrier | Sensor supply / warm-up time | Measuring cycle / transmission interval / lifespan | Links |
|---|---|---|---|---|---|---|
| Alicat Scientific | Alicat IS-Max/Pro | Pressure and flow monitor | 167 | 24 V / 1 sec. | tbd | Proof of intrinsic safety |
| Althen GmbH | NM1-2L-420-ATEX-xxxx | Tilt measuring system | 167 | 24 V / 1 sec. | tbd | Proof of intrinsic safety |
| Boie | Hydrolevel® SPK | Pressure transmitter | 167 | tbd | tbd | Proof of intrinsic safety |
| Endress+Hauser | Cerabar PMC21 / PMP21 / PMP23 | Pressure transducer | 167 | tbd / <=2 sec. | tbd | Proof of intrinsic safety |
| Cerabar PMC51B | Pressure transmitter | 167 | 23 V / 5 sec. | tbd | Proof of intrinsic safety | |
| Cerabar S PMC71 / PMP71 / PMP75 | Pressure transmitter | 167 | 20 V / 10 sec. | tbd | Proof of intrinsic safety | |
| Transmitter Liquiline Compact CM72/CM82 | Transmitter | 167 | 23 V / 38 sec. | 30 min. / 12 h / 2,5 years | Proof of intrinsic safety | |
| Micropilot FMR20B FMR30B | Radar level sensor | 167 | 22 V / 30 sec. | 10 min. / 24 h / 450 d | Proof of intrinsic safety | |
| Microwave unit Micropilot FMR6x-BBA | Level radar | 167 | 24 V / 60 sec. | tbd | Proof of intrinsic safety | |
| TMT7x | Temperature transmitter | 167 | tbd | tbd | Proof of intrinsic safety | |
| Waterpilot FMX21 | Hydrostatic level measurement | 154 | 20 V / 6 sec. | tbd | Proof of intrinsic safety | |
| Hach Lange GmbH | GS2440EX | Gas Sensing Device | 167 | 21 V / <30 sec. | tbd | Proof of intrinsic safety |
| HYDAC Electronics GmbH | HDA 4xx | Pressure transmitter | 167 | tbd | tbd | Proof of intrinsic safety |
| KROHNE Messtechnik GmbH | SMARTPAT COND 5200 | Conductivity sensor | 167 | tbd / 50 sec. | tbd | Proof of intrinsic safety |
| SMARTPAT ORP 8150 | ORP sensor | 167 | tbd | tbd | Proof of intrinsic safety | |
| SMARTPAT PH 8320 | Digital pH sensor | 167 | tbd / 20 sec. | tbd | Proof of intrinsic safety | |
| KELLER Druckmesstechnik AG | 23SYEi; 23YEi; 23YMEi; 25YEi; 26YEi; 26YMEi; PT-25YEi | Pressure & temperature transmitter | 167 | 20 V / <5 ms | 5 min. / 12 h / 5 years | Proof of intrinsic safety |
| Microtronics Engineering GmbH | REP01-15 1) | Digital end position sensor | 167 | 15-22 V / 0,1 sec. | 1 min. / 24 h / 10 years | Certificate - simple apparatus |
| Nivus GmbH | i-Series Sensor | Ultrasonic level measurement | 167 | tbd | tbd | Proof of intrinsic safety |
| Pulsar Process Measurement | MicroFlow-i | Process flow measurement radar sensor | 167 | tbd | tbd | Proof of intrinsic safety |
| R. Stahl AG | 9164/13-20-06; 9164/13-20-08 | mA-isolating repeater | 167 | 14 V / tbd | tbd | Proof of intrinsic safety |
| Rosemount | 248 | Temperature transmitter | 167 | 21 V / 5 sec. | 5 min. / 12 h / 1,5 years | Proof of intrinsic safety |
| 2088 | Pressure transmitter | 167 | 20 V / 2 sec. | tbd | Proof of intrinsic safety | |
| Siemens AG | SITRANS P320/420 | Pressure transmitter | 167 | 20 V / tbd | tbd | Proof of intrinsic safety |
| VEGA | Vegabar 8x | Pressure transmitter | 167 | 19 V / 9 sec. | tbd | Proof of intrinsic safety |
| Vegapuls 6x | Radar level gauge | 167 | 22 V / 15 sec. | tbd /tbd / 230 d | Proof of intrinsic safety | |
| Vegapuls C21 | Radar sensor | 167 | 22 V / 10 sec. | tbd /tbd / 230 d | Proof of intrinsic safety | |
| Vegason S6x | Ultrasonic sensor | 167 | tbd | tbd | Proof of intrinsic safety | |
| Vegawell 51/52/72 | Submersible pressure transmitter | 167 | tbd | tbd | Proof of intrinsic safety | |
| 147 | 18,5 V / 2 sec. (error < 0,2%), 10 sec. (error < 0,1%) | tbd | Proof of intrinsic safety | |||
| WIKA | IS-3 | Pressure transmitter | 167 | 19 V / tbd | tbd | Proof of intrinsic safety |
1) The device is a simple apparatus. It is therefore not permitted for use areas with a zone 0 explosive atmosphere.