Ex protection
The portable VEL‑R‑5 is designed for use in areas with a zone 1 explosive atmosphere.
The following conditions must be observed:
- The device is designed for fixed installation and cannot be used as a portable equipment in potentially explosive atmospheres.
- Equipment must be installed in a place with low risk of mechanical impact and shall be adequately protected from falling objects.
- Non-metallic parts of the equipment enclosure shall be protected from direct sunlight.
- The plastic surface of the housing of the device exceeds the limit specified in the standard, so it must be protected against electrostatic charging. Cleaning should only be done with a damp cloth.
- Do not open the housing in the presence of an explosive atmosphere.
- The built-in battery shall be replaced in a non-hazardous area and only the original battery supplied by the manufacturer may be used for replacement. It is forbidden to recharge the power supply cell in the device.
- Only the manufacturer's original spare parts must be used.
- A mounting distance of min. 50 mm must be maintained on all sides to prevent any impurities.
II 1/2G Ex
ia/ib IIB T4...T3 Ga/Gb
The seperation surface between the category 1 and cotegory 2 part is the external thread for process installation. In case of a vertical installation with the Radar lens looking downwards, below this thread the VEL‑R‑5 complies to category 1, above it, it is of category 2.
| 1 | VEL‑R‑5 | 2 | Closed container |
Dependence between temperature casses and ambient temperatures:
| Temperature class | Maximum ambient temperature |
|---|---|
| T4 | -20...+55 °C |
| T3 | -20...+70 °C |