Sensor settings

Input window "Sensor settings"

1 Freely selectable designation for the measurement value determined using the Modbus measurement channel
2 Selection whether the Modbus measurement channel should be active
Off Measurement channel deactivated
On Measurement channel activated
3 Selection of the sensor type
Distance Distance sensor, i.e. the sensor provides a distance in metres
Pressure Pressure sensor, i.e. the sensor provides a pressure reading in bar
4 Address from which the registers should be read. Two registers from the sensor are read at a time and interpreted as a 32-bit float with "HI-LO" word order (HI word at the lower register address, LO word at the higher register address).
5 Address of the modbus server
6 Function code to be used for accessing the register
FC03 Read Holding Registers
FC04 Read Input Registers
7 Button to apply the settings
Note: To save the settings, the "Save" button below the "Smart Actions" configuration section must also be clicked.