Compatible sensors

Microtronics Engineering GmbH is constantly testing various sensors with mA output or Modbus server interface (RS485) for compatibility with the Lizzox Pure Flood . If your sensor is not on the list, please contact us at support@microtronics.com. We will then check whether your sensor can be used together with the Lizzox Pure Flood and determine the recommended configuration settings.

Note: The specifications for sensor supply and warm-up time are recommendations. The required warm-up time depends on the operative conditions and must be determined by the user in the respective application and installation situation. If the current consumption of the sensor exceeds the capacity of the sensor supply of the Lizzox Pure Flood , the correct function can be established if necessary by increasing the sensor supply (within the system limits). The information in the following table is without guarantee and Microtronics Engineering GmbH assumes no responsibility if an installation set up based on the information contained in the table does not function as expected.

Sensors with mA output
Manufacturer Designation Type Measurement range Sensor supply / warm-up time
Endress+Hauser Cerabar PMC11/PMC21/PMP11/PMP21 Pressure transmitter 0...40 bar 15 V / 2 sec.
Cerabar PMC51B Pressure transmitter 0...40 bar 15 V / 10 sec.
Cerabar PMC71 Pressure transmitter 0...40 bar 15 V / 10 sec.
Micropilot FMR20B/30B Radar sensor - level up to 30 m 15 V / 15 sec.
Micropilot FMR60B Radar sensor - level 0...50 m 15 V / 15 sec.
KELLER Pressure AG Series 26x Level probe 0...25 bar 15 V / 1 sec.
Krohne OPTIBAR LC1010C Level probe 0...10 bar 15 V / 4 sec.
OPTIWAVE 1520 Radar sensor - level 0...10 m 15 V / 20 sec.
VEGA Vegabar 83 Pressure transmitter -1...1000 bar 15 V / 10 sec.
Vegapuls 6X Radar sensor - level 0...120 m 15 V / 15 sec.
Vegapuls C11 Radar sensor - level 10 m 15 V / 15 sec.
Vegapuls C21 Radar sensor - level 20 m 15 V / 15 sec.
Vegapuls C23 Radar sensor - level 30 m 15 V / 15 sec.
Vegawell 52 Submersible pressure transmitter 0...60 bar 15 V / 2 sec.

Sensors with Modbus server interface
Manufacturer Designation Type Measurement range Sensor supply / warm-up time
Boie Hydrolevel SPK Pressure sensor - level 0...20 bar 15 V / 1 sec.
KELLER Pressure AG PAA-33X Piezoresistive pressure transmitters (absolute pressure) refer to manufacturer documentation 15 V / 1 sec.
PAA-36XW Piezoresistive level probe (absolut pressure) refer to manufacturer documentation 15 V / 1 sec.
Serie 26X Pressure probe 0...25 bar 15 V / 1 sec.
VEGA Vegapuls C21 Radar sensor - level up to 20 m 15 V / 15 sec.
Vegapuls C23 Radar sensor - level up to 30 m 15 V / 15 sec.

Note: Some of the pressure sensors listed in the table are available with absolute or relative pressure measurement. Please note that the Lizzox Pure Flood only supports absolute pressure measurement.