Control module

The control module determines the setpoints for the outputs.

The following table specifies the relevant parameters for the module:

Configuration section Mode Parameter Explanation
Output channels Off --- ---
Ext. warmup time Ext. warmup time Indicates the amount of time that an output channel is switched on in "Ext warmup time" mode before the measurement
Digital --- ---
Freq
Pulse
Measurement channels ‑>Trigger
Digital
Cnt.Day
Cnt.Intrvl.
4-20 mA
0-20 mA
0-2 V
0-10 V
OS If this checkbox has been selected, the setpoint at the switchable sensor supply output VOUT is controlled by the trigger function. The setpoint entered via the interface is ignored in that case.
O3 If this checkbox has been selected, the setpoint at the switchable sensor supply output VEXT is controlled by the trigger function. The setpoint entered via the interface is ignored in that case.
OD

Output in mode "digital":

If this checkbox has been selected, the setpoint at the isolated switch contact (NO, CC) is controlled by the trigger function. The setpoint entered via the interface is ignored in that case.

Output in mode "Freq" or "Impulse":

If this checkbox has been selected, the output of the frequency or the impulses/min at the isolated switch contact (NO, CC) is only released when trigger is active. When trigger is not active, the output channel is set to "off (contact open)".
Cnt.Inf. --- ---
Internal channels -> Trigger --- OS See explanation for parameter "OS" for "measurement channels -> trigger"
O3 See explanation for parameter "O3" for "measurement channels -> trigger"
OD See explanation for parameter "OD" for "measurement channels -> trigger"