Technical details about the energy supply
Schematic diagram of the energy supply (applies to each component of the myDataconC3+ )
| myDatalogC3xx | myDatalogC3e 12UI/2Rel | myDatalogC3e 3mA/6Rel | |
|---|---|---|---|
| V IN | 9...32 VDC (+/-10 %) | 9...32 VDC (+/-10 % ) | 9...32 VDC (+/-10 % ) |
| Power consumption 1) (sithout sensors) |
typ. 5 W max. 9 W |
typ. 5 W max. 9 W |
typ. 5 W max. 9 W |
| Input capacity | 330 µF | 330 µF | 330 µF |
| Fuse | 1,6 A T | 1,6 A T | 1,6 A T |
| Reverse voltage protection | yes | yes | yes |
1) applies to ongoing operation. A current peak is caused by the input capacity at the time of activation.
All components of the myDataconC3+ (i.e. data logger and extensions) are equipped with a relatively large input capacity (330 µF ). For the myDatalogC3xx, this serves among other things to ensure a reliable switchover to the integrated rechargeable buffer battery in the event of a supply voltage failure. When selecting the power supply please ensure that it is able to supply the required initial current. A selection of compatible power supply units is provided in the chapter Power supply. The supply voltage input is also equipped with a diode to protect against polarity reversal and 1,6 A T fuses.