Relays on output extension (RELAY1-3, RELAY 4-6)
3 relays are grouped to a common root. In idle state, the make contact of all relays are open (normally open).
Important: Up to 3 A can
flow through each of the relays in a group. However, the current through the common root of a
group (CC) must not exceed 6 A
.
Equivalent circuit diagram for the relays
| Proof voltage (CC, NO) | 230 V AC |
| galv. separation | 2,5 kV AC |
| Umax | 230 V AC ,30 V DC |
| Imax | 3 A 1) |
| Pmax | 750 VA |
1) applies to one relay. However, the current through the common root (CC) must not exceed 6 A gilt pro Relais.