Compatible sensors

Microtronics Engineering GmbH is constantly testing various sensors with mA output for compatibility with the Jellox Analog Pro . If your sensor is not on the list, please contact us at support@microtronics.com. We then check whether your sensor can be used together with the Jellox Analog Pro and determine the recommended configuration settings and the expected battery lifespan.

Note: The specifications for sensor supply and warm-up time are recommendations. The battery lifespan was calculated based on these values. The lifespan is always an "up to" specification. The required warm-up time and the resulting lifespan depend on the application conditions and must be determined by the user in the respective application and installation situation. If the current consumption of the sensor exceeds the capacity of the sensor supply of theJellox Analog Pro , the correct function can be established if necessary by increasing the sensor supply (within the system limits). The information in the following table is without guarantee and Microtronics Engineering GmbH assumes no responsibility if an installation set up on the basis of the information contained in the table does not function as expected or if the expected lifespan is not achieved.
ManufacturerDesignationTypeSensor supply / warm-up timeMeasuring cycle / transmission interval / lifespanLinks
Alicat ScientificAlicat IS-Max/ProPressure and flow monitor 22 V / tbd tbd Proof of intrinsic safety
Althen GmbH NM1-2L-420-ATEX-xxxx Tilt measuring system 22 V / 1 sec. 5 min. / 24 h / 2000 d

1 min. / 24 h / 640 d

Proof of intrinsic safety
BoieHydrolevel® SPKPressure transmitter20 V / 0,2 sec. 5 min. / 24 h / 1100 d Proof of intrinsic safety
CS Instruments FA515 Ex Dew point sensor 18 V / tbd tbd Proof of intrinsic safety
Endress+HauserCerabar PMC51B Pressure transmitter 19 V / 5 sec. 0,5 min. / 24 h / 80 d

5 min. / 24 h / 800 d

Proof of intrinsic safety
Cerabar S PMC71 / PMP71 / PMP75 Pressure transmitter19 V / 10 sec. tbd Proof of intrinsic safety
Transmitter Liquiline Compact CM72/CM82 Transmitter 22 V / 38 sec. 30 min. / 12 h / 2,5 years Proof of intrinsic safety
Micropilot FMR20B / FMR30BRadar level sensor 21 V / 30 sec. 10 min. / 24 h / 450 d Proof of intrinsic safety
TMT7x Temperature transmitter tbd tbd Proof of intrinsic safety
Waterpilot FMX21 Hydrostatic level measurement 19 V / 6 sec. 5 min. / 24 h / 300 d Proof of intrinsic safety
HYDAC Electronics GmbH HDA 4xx Pressure transmittertbd tbd Proof of intrinsic safety
KELLER Druckmesstechnik AG23xEi / 25xEi / 26xEiPressure & temperature transmitter19 V / <5 ms 5 min. / 12 h / 5 years Proof of intrinsic safety
KROHNE Messtechnik GmbH SMARTPAT COND 5200 Conductivity sensor 22 V / 45 sec. 60 min. / 24 h / 2 years Proof of intrinsic safety
SMARTPAT ORP 8150 ORP sensor 22 V / 20 sec. 30 min. / 24 h / 2 years Proof of intrinsic safety
SMARTPAT PH 8320 Digital pH sensor22 V / 15 sec. 30 min. / 24 h / 2,5 years Proof of intrinsic safety
Microtronics Engineering GmbHREP01-15 Digital end position sensor15-22 V / 0,1 sec. 1 min. / 24 h / 10 years Certificate - Simple apparatus
Nivus GmbH i-3Ultrasonic level measurement 18 V / 4 sec. 15 min. / 24 h / 4,5 years Proof of intrinsic safety
Pulsar Process Measurement MicroFlow-i Process flow measurement radar sensor18 V / 4 sec. 10 min. / 12 h / 2,5 years

5 min. / 12 h / 1,5 years

Proof of intrinsic safety
R. Stahl AG9164/13-20-06; 9164/13-20-08mA-isolating repeater13 V / tbd tbd Proof of intrinsic safety
Rosemount248Temperature transmitter20 V / 5 sec. 5 min. / 12 h / 1,5 years Proof of intrinsic safety
2088Pressure transmitter19 V / 2 sec. tbd Proof of intrinsic safety
Siemens AGSITRANS P320/420Pressure transmitter19 V / tbd tbd Proof of intrinsic safety
SulfiLogger A/SSulfiLogger X1Gas sensor21 V / tbd tbd Proof of intrinsic safety
VEGAVegapuls C21Radar sensor17 V / 10 sec. 5 min. / 24 h / 230 d Proof of intrinsic safety
Vegapuls 6xRadar level gauge21 V / 15 sec. tbdProof of intrinsic safety
Vegabar 8xPressure transmitter 18 V / 10 sec. tbdProof of intrinsic safety 
Vegason S6xUltrasonic sensortbd tbd Proof of intrinsic safety
Vegawell 51/52/72 Submersible pressure transmitter 15 V / 2 sec. (error < 0,2%)5 min. / 24 h / 485 d Proof of intrinsic safety