| Device does not respond (status LED always off). |
|
| Communication problems |
- Load the device log from the 4-Channel
Data Logger MBM using
the DeviceConfig
(see "Log" tab). A list of all the possible error codes is included in the chapter "Log
entries and error codes" (see Log entries and error codes).
- The capacity of the energy store in the power supply unit is virtually depleted.
|
| The connection via the external SIM card is not working. |
- The chargeable feature "Activation code VPN SIM (300539)" has not been released.
- Check whether the external SIM card has been inserted correctly (see Inserting/replacing the SIM card).
- Check whether the configuration data (PIN, APN, username and password) have
been set correctly via the DeviceConfig
(see "GSM" tab).
- Check whether the PIN code (if required by the SIM card) has been set
correctly by the DeviceConfig
.
|
| Not all or no data is available on the server. |
- The connection was aborted during the transmission, which is indicated by a time-out entry in the connection list (see "myDatanet Server Manual " 805002). Solution: Initiate a transmission or wait for the next cyclical transfer.
- The assignment of the device and site is not correct (see Site).
|
| Data at universal input is not plausible. |
|
| The measurement values of the external temperature sensor are not
plausible. |
|
| The data of the onBoard RS485 interface is not plausible. |
|
| The data of the RS485 interface of the interface card is not plausible. |
- The chargeable feature "Activation code RS232 (300541)" has not
been released..
- Check the cable connections (see RS485 interface extension)
- Check whether the interface configuration matches the sensor output signal
(see Modbus interface).
- Check the settings of the 4-pin dip switch for swtiching on/off the terminal
resistor or clamp resistance (see RS485 interface extension).
- Check whether the Modbus address and the server address have been selected
correctly upon configuration of the modbus measurement channels (see Modbus measurement channels).
|
| The exact geographic position could not be determined. |
- The chargeable feature "Activation code RS232 (300541)" has
not been released.
- Check whether the optionally available GNSS receiver has been installed
correctly.
- The GPS antenna must be attached in such a position that there is a clear view
to the sky.
- Check whether app version 02v010 or higher is installed on the device.
|
| The alarm state of a measurement channel was not identified. |
- Increase the measurement cycle
|
| The alarm state was not transmitted although the data is present. |
- Check the alarm settings of the measurement channel
- The connection was aborted during the transmission, which is indicated by a time-out entry in the connection list (see "myDatanet Server Manual " 805002). Solution: Initiate an Aloha transmission or wait for the next cyclical transmission.
|
| The alarm message was not sent although the alarm was signalled. |
- Check the settings of the alarm schedule (see "myDatanet Server Manual " 805002)
- Check the address data of the alarm schedule (see "myDatanet Server Manual " 805002)
|
| Isolated switch contact is not working. |
- Disruption to the voltage that is conducted via the relays
|